308
1.5 Dio Unit (DEC102A51)
Adaptor
Factory preset before shipment
C/C : Centralized controller
C/D : Connectable Devices or Facility equipment
Switch
Condition
Factory preset before shipment
DS1
Range of address No.
1-00, 01, 02, 03
DS2
A1 - AM
Abnormal in the open condition
DS4-1
Power failure, then after power recovery
Stop
DS4-2
Communication abnormal
Stop
DS4-3
Last command priority or C/C only
Last command priority
DS4-4
Operation commands from C/C reach to C/D , but no
operation.
No abnormality signal to C/C
DS5
Of abnormal in C/D,
CD- D1~4 is “turned off”.
DS6-1
Mask time for abnormal input after operation command
from C/C
10 seconds
DS6-2
After error of C/D is recovered
Automatic reset
DS6-3
Abnormal input + stop state of C/D
Error display on C/C
DS6-4
Forced stop command from C/C
C/D stop
SS1
Continuous output “Con” / Instantaneous output “Ins”
Continuous output
TNa
“a” contact or “b” contact for CD- D1~4
“a” contact
DS3
Number of C/D
4
“a” : arbeit, “b” : break
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...