3.2 Main Specifications and Functions of the Equipment
11
Outline of D-BACS System
Outline of System
When using 1 unit of IPU
When using 1 unit of intelligent touch controller
When using one central remote controller
When using 1 unified ON/OFF controller
When using one unit of schedule timer
Note: For the schedule timer, take the electric power supply from the indoor unit.
intelligent
Manager III
Remote
controller
Remote
controller
Up to 1024 groups for group control
Up to 2048 units
for individual control
Power source
Single phase 100 - 240V
Maximum length of communication
wires for central control: 1 km
intelligent
touch controller
Remote
controller
Remote
controller
Up to 64 groups for group control
(however, up to 128 units can be controlled)
Up to 64 units
for individual control
Power source
Single phase 100 - 240V
Maximum length of communication
wires for central control: 1 km
Central
remote controller
Remote
controller
Remote
controller
Up to 64 groups for group control
(however, up to 128 units can be controlled)
Up to 64 units
for individual control
Power source
Single phase 100 - 240V
Maximum length of communication
wires for central control: 1 km
Unified
ON/OFF controller
Remote
controller
Remote
controller
Up to 16 groups for group control
(however, up to 128 units can be controlled)
Up to 16 units
for individual control
Power source
Single phase 100 - 240V
Maximum length of communication
wires for central control: 1 km
Schedule time
Electric power supply
for schedule timer
Maximum length of communication
wires for central control: 1 km
Up to 128 indoor units
can be controlled
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...