1.10 Functions
213
Interface for Use in BACnet
®
1.10.2 Major Functions of Air-conditioner Devices (Incl. Adaptors) to be Connected
When the air-conditioners are hooked up with the Interface for use in BACnet
®
, the following functions can be performed
and monitored from the master station or the central monitor panel.
Note :
1. *When set at the unit, the status is not notified to upper devices and cannot be monitored from them.
2.
U
: Available for certain models only.
Function
VRV System
Hi Sky Multi
SkyAir
(adapter for
SkyAir
connection)
Duct-
connected type
air conditioner
(central control
adapter)
HRV
Room air
conditioners
(general-
purpose
adapter)
Remarks
Start / stop operation
and monitoring
{
{
{
{
{
{
Air conditioner
malfunction
notification
{
{
{
{
{
{
Room temperature
monitoring
{
{
{
{
×
×
Temperature setting
and monitoring
{
{
{
{
×
×
Air-conditioning mode
setting and monitoring
{
{
{
{
×
×
Air-conditioning mode
switching is effective
only for indoor units for
which cool / heat
selection is permitted.
Remote-control mode
setting and monitoring
{
{
{
{
{
×
Filter sign monitoring
and reset
{
{
{
×
{
×
Thermostat status
monitoring
{
{
{
×
×
×
Compressor
operation status
monitoring
{
{
{
×
×
×
Indoor fan operation
status monitoring
{
{
{
×
{
×
Heater operation
status monitoring
{
{
{
×
×
×
Humidifier operation
status monitoring
{
{
{
×
×
×
Air direction setting
and monitoring
{
{
{
×
×
×
Air flow rate setting
and monitoring
{
{
{
×
U
Monitoring
only
×
Forced thermostat
disable setting and
monitoring
{
*
{
{
×
×
×
Energy saving
(set temperature shift)
{
{
×
×
×
×
Accumulated power
{
{
U
×
U
×
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...