1.1 Features
171
intelligent Manager
Interlock control of tanks and pumps
Water pump
Water level sensor
Water level data
On/off commands
Interlock control of lighting or key
management systems and air conditioning
equipment
The system can monitor signals that turn off the lights
or lock the key management system and shut down
the air conditioning equipment in the corresponding
area. This prevents wasted electricity if tenants acci-
dentally leave the air conditioning on when they leave.
If the data from the sensors indicate the temperature
is lower outside than inside, the system can automati-
cally shut down the air conditioner and switch on the
air intake fans to save electricity.
If a fire alarm signal is received, the system can auto-
matically shut down the air conditioning or ventilation
equipment in the affected area.
Turning off the
A/C and lighting
Light switch
Off in
corresponding area
Key management
device
Locking signal
Interlock control of outdoor temperature
sensors and air conditioning
and ventilation equipment
Air conditioner
Indoor
temperature
Outdoor
temperature
sensor
Outdoor
temperature
Overall judgment
Off
command
ON
Air supply fan
Interlock control of fire alarms and
air conditioning or ventilation equipment
Ventilation fan
Fire alarm
device
Fire
Alarm
signal
Off command to
affected area
Blower
Adaptors to extend the equipment management capabilities of lntelligent Manager .
Di unit
(DEC101A51)
Air conditioner
Examples of interlock control
This dedicated monitoring
adaptor keeps track of the op-
eration status and malfunc-
tions of connected equipment.
In addition to the monitoring
functions of the Di unit, this
adaptor adds on/off and other
operation capabilities.
Dio unit
(DEC102A51)
D -Ai unit
(DAM101A51)
This temperature sensor unit
measures the outdoor temper-
ature.
Automated control
The system can turn pumps on and off based on the
water storage volume, and thereby maintain a con-
stant water level.
Turning off power when people forget
Processing of analogue data
Processing of alarm signals
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...