5.3 Simplified Remote Controller <BRC2C51 (BRC2A51)>
87
Remote Controllers
Note:
1. Setting is carried out in the group mode, however, if the mode number inside the parentheses is selected, indoor units
can also be set individually.
2. The SECOND CODE number is set to "01" when shipped from the factory.
3. Do not make any settings not given in the table on the left.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, "
88
" may be displayed in the LCD in order for the remote controller to initialize
itself.
6. This mode is used to set the time until the display time to clean air filter lights up when using central remote controller.
Mode No.
Note) 1
FIRST
CODE
No.
Description of Setting
SECOND CODE No. Note) 2
01
02
03
10(20)
Note) 6
0
Filter Contamination - Heavy/Light
(Setting for spacing time of display
time to clean air filter)
(Setting for when filter
contamination is heavy, and spacing
time of display time to clean air filter
is to be halved)
Long Life Filter
Light
Approx.
2,500 Hrs.
Heavy
Approx.
1,250 Hrs.
—
Standard Filter
Approx.
200 Hrs.
Approx
100 Hrs.
3
Spacing Time of Display Time to Clean Air Filter Count
(Setting for when the filter sign is not to be displayed)
Display
Do Not Display
—
12(22)
1
ON/OFF Input from Outside. (Setting for when forced
ON/OFF is to be operated from outside.)
Forced OFF
ON/OFF
Operation
2
Thermostat Differential Changeover (Setting for when
using the remote sensor)
FXC(Q), FXF(Q), FXK(Q) or FXH(Q) only
1°C
0.5°C
—
13(23)
0
High Air Outlet Velocity (Setting for when installed in a
high ceiling)
FXF(Q) only
2.7m or less
More than 2.7 m;
3.0 m or less
More than 3.0 m;
3.5 m or less
1
Selection of Air Flow Direction (Setting for when a
blocking pad kit has been installed)
FXF(Q) only
4-way flow
3-way flow
2-way flow
15(25)
1
Humidifying with thermostat OFF
Not equipped
Equipped
3
Drain pump operation with humidifying
Not equipped
Equipped
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...