286
1.2 <KRP2A61 / KRP2A62 / KRP2A53> Wiring Adaptor for Electrical Appendices (1)
Adaptor
(7) Output display signals
Operation output terminals (W1 and W2) and malfunction output terminals (W3 and W4) are non-voltage constant contact
output.
(Allowed electric current per contact is between 10 mA ~ 3 A.)
Note:
If using a 220
~
240V power supply, keep transmission wiring at least 50 mm away from incoming power supply wiring.
Display output is described by system in the below table.
Note:
If rewiring F1 and F2 after running the system, turn ON power for 5 minutes, then turn it OFF and ON again. Changes to
wiring can sometimes disable control from the wiring adaptor.
C : 1PA63642B
Digital
contact
Both Ry1 and Ry2 OFF
(Open)
Ry1 only ON
(Close)
Ry2 only ON
(Close)
Operation
status
All zones OFF
At least one unit running normally, no
malfunction
Even 1 unit stopped due to malfunction or
malfunction of transmission between
adaptor and indoor unit
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...