146
1.11 Error Diagnosing Function
Control Devices
1.11
Error Diagnosing Function
This central remote controller is provided with a diagnosing function, for when an indoor unit stops due to malfunction. In
case of actuation of a safety device, disconnection in transmission wiring for control or failure of some parts, the operation
lamp, inspection display and unit No. start to flash; then, the malfunction code is displayed. Check the contents of the
display, and contact your DAIKIN dealer because the above signs can give you the idea on the trouble area.
The display "
" flashes under the group No. where the indoor unit that has stopped due to malfunction.
[Registration]
1.
Press the ARROW KEY BUTTON to call up the group that has stopped due to malfunction.
The unit No.
the malfunction code is flashing because of an error failure.
3P124623-3A
1
2
3
00 01 02 03
1
2
3
L
UNIT No.
C
Operation
lamp
Maintenance
display
Unit No.
Malfunction
code
Error content
64
Indoor air thermistor error
65
Outdoor air thermistor error
68
HVU error (Ventiair dust-collecting unit)
6A
Dumper system error
6A
Dumper system error + Thermistor error
6F
Simple remote controller error
6H
Door switch (Ventiair dust-collecting unit), relay harness fault
(Ventiair dust-collecting/humidifier unit)
94
Ventiair internal transmission error
(between total enthalpy – fan unit)
A0
Indoor unit · external safety device error
A1
Indoor unit · BEV unit (Sky-Air connection unit) PC board
assembly fault
A1
Indoor unit · PC board assembly fault
A3
Indoor unit · Drain level error (33H)
A6
Indoor unit · Fan motor (51F) lock, overload
A7
Indoor unit · Fan direction adjustment motor (MA) error
A9
Indoor unit · BEV unit, electric expansion valve motor (20E) error
AF
Indoor unit · Malfunctioning drain
AH
Indoor unit · Dust-collector error
AJ
Indoor unit · Insufficient capacity setting, address setting fault
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...