12.4 Outline of Functions
245
Interface for use in LONWORKS
®
<Rough Estimate of Number of Groups Connected >
(Assuming that acknowledged service is 10 items per
second on a 30-second interval data collection cycle.)
-
Acknowledged Service (possible communication volume): 10 items/second
This is one of the performance features of a Interface for LONWORKS
®
. It can process 10 items per second.
-
30-second interval data collection cycle
This is the time interval whereby device data (status) is collected from the central monitoring panel. In this case, the
data regarding the connected A/C units is collected in 30 seconds. This figure differs with respect to the specifications
of the central monitoring panel.
-
Interface for LONWORKS
®
performance
...
Acknowledged Service: 10 items/second (fixed value)
-
Central Monitoring Panel performance
...
30-second data collection cycle
10 items per second being collected for 30 seconds translates into a total of 300 control items.
T = 10
×
30 = 300 items
Number of control items per group: Assuming the number of items per group is 23, the number of groups connectable
is 13.
n = T
÷
(No. of control items per group) = 300
÷
23 = 13 groups
-
Interface for LONWORKS
®
performance
...
Acknowledged Service: 10 items/second (fixed value)
-
Central Monitoring Panel performance
...
60-second data collection cycle
10 items per second being collected for 60 seconds translates into a total of 600 control items.
T = 10
×
60 = 600 items
Number of control items per group: Assuming the number of items per group is 23, the number of groups connectable
is 26
n = T
÷
(No. of control items per group) = 600
÷
23 = 26 groups
-
Interface for LONWORKS
®
performance
...
Acknowledged Service: 10 items/second (fixed value)
-
Central Monitoring Panel performance
...
120-second data collection cycle
10 items per second being collected for 120 seconds translates into a total of 1,200 control items.
T = 10
×
120 = 1,200 items
Number of control items per group: Assuming the number of items per group is 23, the number of groups connectable
is 52
n = T
÷
(No. of control items per group) = 1,200
÷
23 = 52 groups
Control and Monitoring Items
n (individual groups)
Max. number of
groups connected
Remarks
23 items (All)
13 groups
- One LON can monitor up to 300 items.
- The maximum number of control and monitoring items is 23 per A/
C unit. If the number of control and monitoring items per A/C unit is
assumed as ‘n’, the number of A/C groups connectable would be:
<Note: The maximum No. of A/C groups is 64.>
20 items
15 groups
18 items
16 groups
16 items
18 groups
15 items
20 groups
12 items
25 groups
10 items
30 groups
4 items
64 groups
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...