350
2.6 <KRP928B2S> Interface Adaptor for DIII-NET (RA)
Adaptor
<Switch Settings>
NOTE
Other countries
ON
“Automatic” operation is available from the central controller.
Japan
Destination
SW3-3 setting
What Happens
OFF
(Factory setting)
(2) Group number settings (SW1 and SW2-1 to SW2-3)
Set these when using the central controller. (Set to the
side.) Do not set more than one unit to the same number.
Stops if the unit was stopped before the power outage and runs if it was running.
Stops after recovering from a power outage
OFF
(Factory setting)
ON
SW2-4 setting
What Happens
Last command priority
Constant contact input
Instantaneous contact
input (factory setting)
What Happens
Control mode
S1
operating mode
SW3-2
setting
SW3-1
setting
OFF
OFF
ON
ON
Invalid
z
z
Upper
group NO.
1—
2—
3—
4—
5—
6—
7—
8—
1
1 2 3
0
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
SW1
setting
Lower
group NO.
0 0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
1
1 2 3
0
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
4
4
4
4
4
4
4
4
SW1
setting
Lower
group NO.
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
4
4
4
4
4
4
4
4
SW2
setting
Open the Kit’s case and set the switches on the circuit board.
(1) For Overseas / Japanese unit setting (SW3-3)
Room air conditioners, different methods are used for setting the temperature in automatic mode, so this switch
needs to be set.
Turn the power on after all the switches have been set.
Settings made while the power is on are invalid.
“Automatic” operation is not available from the central controller.
When using “automatic” operation using the wireless remote controller, the central
controller displays automatic cooling (heating) and 25
°
C. Even if the temperature is
changed, it will return to 25
°
C after a while.
However, these settings do not need to be made when using the schedule timer independently.
(The settings are needed when used in conjunction with another DCS Series central controller.)
In this case, the schedule timer performs an auto address after the power is turned on, so new group numbers are
automatically set. Settings made using the switches will be overwritten.
NOTE also that a separate timer power source is needed when using the schedule timer independently.
Power source specs: DC 16V, +10%, -15%, 200mA.
Recommended power source: Omron S82J-01015A. (Should be used with the output voltage adjusted to the center, DC 16V.)
(3) Settings when recovering from a power outage (SW2-4)
This selects whether to restart operation when the power comes back on after a power outage occurred
during operation. This setting is given priority in cases where the indoor unit has an auto start ON / OFF
jumper. Note also that regardless of whether switch SW2-4 is on or off, the operating mode, set temperature,
fan direction and speed settings, and remote control prohibition status are stored.
The operating status of the air conditioner is reversed
by an instantaneous input of 100 msec or more.
Contact - Open to close: air condition runs.
Close to open: air conditioner is stopped (NOTE 1).
Contact - Open to close: air condition stops (forced
stop). Close to open: no change in operating status.
Forced stop or remote
controller permission input
ON / OFF control is rejected (operate /
stop / timer prohibition) (NOTE 2).
During a forced stop, all remote
controller actions are prohibited.
NOTE1: Since central equipment and HA JEM-A-compatible equipment both use last command priority, the contact status and
operating status of the air conditioner might not match sometimes.
Example: If the unit is run from the central controller while the air conditioner is stopped with an open contact, the
contact will be open and the unit will be running.
NOTE2: Operating mode and fan direction and speed settings can be changed.
(4) Contact input function settings (SW3-1 to SW3-2)
When using contact input (S1), choose one of the following functions.
Run / stop Input
Contact specs
No-voltage minute electric current contact
(Minimum applicable load DC 12V, 1mA or lower)
Total wire length max: 100m
KRP928B2S
S1
CA
CB
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...