12.5 LON Communication Specifications
Interface for use in LONWORKS
®
(3) Send on Delta Temperature: Detect Minimum Temperature Change
The bound output network variables will be sent to notify the system when there is a change in temperature that is
greater than the above specified value between two consecutive transmissions.
(4) Delay Start Up: Transmission Start Delay Time after Start Up
The time lag between turning on the LON node and starting the LON communications. This setting is useful for
avoiding communication congestion when LON nodes on the network simultaneously start up.
(5) Range Maximum: Maximum Transmission Limit
The number of messages transmitted from the Interface for LONWORKS
®
will effectively controlled by the bound
output network variables. It also specifies the number of messages to be sent per minute. This is used to limit the
number of messages to be consecutively sent from the nodes when they are started up.
-
Items to be transmitted are the following 6 items: On/Off Status, Room Temperature, Filter Sign, Error Status,
Error Code and A/C Communication Status.
-
The Interface for LONWORKS
®
collects room temperature data every 12 seconds, so any heartbeat transmission set
at a lower time interval will ultimately result in a 12-second transmission interval.
Control items
Values and meanings
Minimum Transmission Interval
sec.
0 seconds and 1.0
-
1200.0 seconds
0: No control, Default Value: 0
Heartbeat Transmission
sec.
0 seconds and 10.0
-
1200.0
0: No control, Default Value: 0
Detect Minimum Temperature
Change
°
C
Temp. (
°
C): 0.10-10.00, Default Value: 0.10
Transmission Start Delay Time after
Start Up
sec.
60.0-1200.0, Default Value: 60.0
Maximum Transmission Limit
(messages/sec.)
--
0 and 1-6000, 0: No control, Default Value: 0
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...