154
2.5 Initial Setting
Control Devices
3. MAIN/SUB Changeover Switch Setting
With two unified ON/OFF controllers, centralized control (indoor units) is possible from different locations. In this kind
of set-up, it is necessary to set the MAIN/SUB changeover switch.
One of the two unified ON/OFF controllers (1) · (2) is set to “MAIN” while the other is set to “SUB”.
4. Setting of the Sequential Operation Function
The unified ON/OFF controller is equipped with a sequential operation function that sequentially turns indoor units on
in 2-second intervals during unified operation. (Sequential operation is factory set to “ON.”) To switch sequential
operation ON or OFF, set as follows.
Note:
The sequential operation function is designed to reduce the load on the power supply equipment, but does not guarantee
that compressors will not be started simultaneously. You cannot therefore count on a capacity reduction effect by power
supply equipment breaker selection.
5. Control Mode Selector (DS2)
The following four patterns of control mode can be set.
Note:
“
” Indicates the position of switches.
Set control mode before turning power supply ON.
When used in conjunction with central remote controller, the control modes of the central remote controller has the
priority.
6. Forced Reset Switch (SS1)
When changing the setting of the connector for setting master controller, etc., you can reset simply by setting it to the
reset side once and returning to the normal side, without turning the power OFF.
(For normal operation, set the switch to the normal side.)
C: 1P162827
Control Mode Individual
Centralized
Timer Operation Possible by
Remote Controller
ON/OFF Control Impossible by
Remote Controller
Content
Operation/stop is
controlled by both unified
ON/OFF controller and
remote controller.
After operated by unified
ON/OFF controller,
operation/stop is freely
controlled by remote
controller until stopped by
unified ON/OFF controller.
When used in conjunction with
schedule timer, operation/stop
is controlled freely by remote
controller during the set time
but operation is not available
when schedule timer is ON.
Operation/stop is controlled by
unified ON/OFF controller only.
(This unit can not be operated/
stopped by remote controller.)
DS2 Setting
(Factory set)
Unified ON/OFF
controller (1)
Group
No.
1–00
Group
No.
1–15
Max. of 16 groups
Unified ON/OFF
controller (2)
Outdoor unit
Sequential operation
“ON”
(Factory set)
Sequential operation
“OFF”
While holding down the unified stop button, perform forced reset.
While holding down the unified operation button, perform forced reset.
12
CONTROL MODE
DS2
ON
12
CONTROL MODE
DS2
ON
12
CONTROL MODE
DS2
ON
12
CONTROL MODE
DS2
ON
RESET
ON
OFF
RESET
ON
OFF
Normal side
(Factory set)
Reset side
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...