4.4 Remote Controller Thermostat
79
Remote Controllers
Heating
The diagram below shows the operation range of the set temperature / air suction temperature combination in heating
operation:
Example
Assuming the preset temperature above is 24°C, and the suction temperature has changed from 18°C to 28°C
(A --> D):
(This example also assumes there are several other air conditioners, the VRV system is off, and that temperature
changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 25°C (A --> C).
Remote controller thermostat sensor is used for temperatures from 25°C to 28°C (C --> D).
And assuming suction temperature has changed from 28°C to 18°C (D --> A):
Remote controller thermostat sensor is used for temperatures from 28°C to 23°C (D --> B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B --> A).
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near the floor where the
occupants are.When controlling by body thermostat sensor only, the unit may therefore be turned off by the thermostat
before the lower part of the room reaches the preset temperature. The temperature can be controlled so the lower part of
the room where the occupants are doesn’t become cold by widening the range in which thermostat sensor in remote
controller can be used so that suction temperature is higher than the preset temperature.
Preset temperature
(Ts)
˚C
Range in which
thermostat sensor in
remote controller can
be used
Range in which
body thermostat
sensor can be used
Suction temperature (TH1)
Differential
TH1=Ts-1
TH1=Ts+12
≤
33˚C
TH1=Ts+10
≤
31˚C
TH1=Ts+1
≤
31˚C
32
30
28
26
24
22
20
18
16
˚C
12 14 16 18 20 22 24 26 28 30 32 34
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...