5.4 Connection of Devices other than VRV
39
Fundamental of DIII-NET
5.4
Connection of Devices other than VRV
• You can connect adapters and other devices (SkyAir adapter, RA adapter, Di/Dio units, etc.), which are not VRV, to
either indoor-outdoor connection or outdoor-outdoor connection.
• You cannot connect a chiller (which accommodates DIII-NET) to the same DIII-NET to which VRV, SkyAir, and RA
are connected.
- If you connect a chiller which accommodates DIII-NET to a centralized controller, divide the DIII-NET for VRV use
and for the chiller.
[Example]
• The maximum number of adapters, except VRV indoor units, to be connected is 64 units including VRV indoor untis.
- One air conditioner connecting adapter (SkyAir adapter, etc.) is counted as one unit.
- One Di unit is counted as 8 units.
- One Dio unit is counted as 4 untis.
- When the output of a Dio unit is set to an instant contact point, one unit is counted as 2 units.
* Regarding Di/Dio units, if you specify the number of units to be connected to each unit, you can reduce the
number of units connected to one unit.
- One Ai unit is counted as one unit.
- When you use a general sensor, one unit is counted as 2 units.
Chiller
Chiller
You cannot connect a chiller
to the same DIII net.
Dio unit
Dio unit
Connect a chiller to
another DIII network.
You can connect Di/Dio units
and Ai unit to the same DIII net
to which a chiller is connected.
SkyAir Indoor unit
Ai unit
Centralized
Controller
SkyAir adapter
Total 17 units
with 5 units
Di unit
Ai unit
Dio unit
(Regular contact
point setting)
Dio unit
(Instant contact
point setting)
Ai unit
(Using a general sensor)
Counted as 8 units
Counted as 1 unit
Counted as 4 units
Counted as 2 units
Counted as 2 units
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...