1.7 BACnet Object List
Interface for Use in BACnet
®
1.7
BACnet Object List
Central control (lower central control disable) and forced system stop are only available for 000, 064, 128, and 192.
(Note 1) The room temperature is measured with the suction air. Since the indoor unit fan stops when the thermostat is disabled or the
air conditioner is stopped, or in a special operation such as defrosting, temperature measurement may be affected by the heat
exchanger, and may detect and transmit a different temperature from the actual room temperature. For this reason, this value
should be considered as a reference for the room temperature.
If the building management system manufacturer uses this value for system control (e.g., switching the air-conditioning mode or
preset temperature), the manufacturer must take on the whole responsibility.
(Note 2) The air conditioner saves the settings for the temperature, start / stop status, air-conditioning mode, air direction, and air flow
rate in the nonvolatile memory each time they are changed, so that the settings will not be lost when a power cut occurs. This
nonvolatile memory has a write count limit and may cause a failure if it is written exceeding the limit count.
Therefore when the temperature, start / stop status, air-conditioning mode, air direction, and air flow rate of each indoor unit are
automatically controlled from the central monitoring panel, be sure that the number of changes for each setting should not
exceed 7,000 times per year.
Member
number
Standard name
Object name
(XXX represents the air
conditioner number.)
Object
type
Unit
Inactive
Active
Text-1
Text-2
Text-3
Text-4
1
Start / stop (setting) (Note 2)
StartStopCommand_XXX
BO
Stop
Operation
2
Start / stop (status)
StartStopStatus_XXX
BI
Stop
Operation
3
Alarm
Alarm_XXX
BI
Normal
Malfunction
4
Malfunction code
MalfunctionCode_XXX
MI
Normal
Manufacturer specific
5
Air-conditioning mode (setting)
(Note 2)
AirConModeCommand_XXX
MO
Cooling
Heating
Fan
Auto
6
Air-conditioning mode (status)
AirConModeStatus_XXX
MI
Cooling
Heating
Fan
7
Air flow rate level (setting)
(Note 2)
AirFlowRateCommand_XXX
MO
Low
High
8
Air flow rate level (status)
AirFlowRateStatus_XXX
MI
Low
High
9
Measured room temperature
(Note 1)
RoomTemp_XXX
AI
°C
10
Set room temperature (Note 2)
TempAdjust_XXX
AV
°C
11
Filter sign signal
FilterSign_XXX
BI
No
Yes
12
Filter sign signal reset
FilterSignReset_XXX
BV
Reset
13
Remote controller enable /
disable (start / stop)
RemoteControlStart_XXX
BV
Enabled
Disabled
14
Remote controller enable /
disable (air-conditioning mode)
RemoteControlAirConModeSet
_XXX
BV
Enabled
Disabled
15
Blank
16
Remote controller enable /
disable (set temperature)
RemoteControlTempAdjust_
XXX
BV
Enabled
Disabled
(*)17
Central control
(lower central control disable)
CL_Rejection_XXX
BV
Enabled
Disabled
18
Blank
19
Accumulated power
ElecTotalPower_XXX
Accumulator kWh
20
Communication status
CommunicationStatus_XXX
BI
Normal
communication
Communication
error
(*)21
Forced system stop
SystemForcedOff_XXX
BV
Clearance Forced stop
22
Air direction (setting) (Note 2)
AirDirectionCommand_XXX
AV
23
Air direction (status)
AirDirectionStatus_XXX
AI
24
Forced thermostat disable
(setting)
ForcedThermoOFFCommand_
XXX
BO
Clearance Set
25
Forced thermostat disable
(status)
ForcedThermoOFFStatus_
XXX
BI
Clearance Set
26
Energy saving (setting)
EnergyEfficiencyCommand_
XXX
BO
Clearance Set
27
Energy saving (status)
EnergyEfficiencyStatus_XXX
BI
Clearance Set
28
Thermostat status
ThermoStatus_XXX
BI
OFF
ON
29
Compressor status
CompressorStatus_XXX
BI
Stop
Operation
30
Indoor fan status
IndoorFanStatus_XXX
BI
Stop
Operation
31
Heater operation status
HeaterStatus_XXX
BI
Stop
Operation
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...