5.9 Wiring Example for intelligent Touch Controller (DCS601C51)
113
intelligent Touch Controller
5.9.3 PPD (Power Proportional Distribution) Application (DCS002C51)
DCS601C51 (Back side)
kWh-meters
[Field Supply]
Remark
Model/Spec
Arrangement
Equipment
•1 pulse to 1kW·h or 10kW·h pulse width must be
within 40-400m/sec.
•Output relay must be or electronic type only.
•No voltage output.
Pulse
transmitter
Field Supply
kW·h meter
Activation number card included
PCMCIA card included
DCS002C51
DAIKIN
Option for Intelligent
Touch Controller (P.P.D)
Up to 64 groups can be connected
DCS601C51
DAIKIN
Intelligent Touch
Controller
DIII-NET
Power
Supply
3
φ
4W 380-415V
50Hz
Refer to field wiring on previous
page about power supply wiring.
Note)
The power consumption
of the outdoor unit can
be proportionally
calculated for each
indoor unit using the
intelligent touch
controller and the
Power Proportional
Distribution software.
The calculated results
are recorded in the
intelligent touch
controller for 13 months.
The calculated results
can be taken out with
the PCMCIA card so
that the data can be
handled using any
spreadsheet software
including Excel on the
PC.
Outdoor Unit
L3 N
L2
L1
A B C F1F2 F1F2 Q1Q2
CSV output of PPD PCMCIA
[DAIKIN option attached PPD]
DAIKIN
The optional Power Proportional
Distribution (PPD) results can be saved
to a CSV file.
Switch
Power Supply
1
φ
220-240V 50Hz
Power Supply
DIII
Contact Signal
R/C
F1 F2 P1 P2
Indoor Unit
F1 F2 P1 P2
Indoor Unit
Outdoor Unit
L3 N
L2
L1
A B C F1F2 F1F2 Q1Q2
Outdoor Unit
L3 N
L2
L1
A B C F1F2 F1F2 Q1Q2
Outdoor Unit
L3
N
L2
L1
A B C F1 F2 F1 F2 Q1 Q2
Outdoor Unit
L3
N
L2
L1
A B C F1 F2 F1 F2 Q1 Q2
R/C
F1 F2 P1 P2
Indoor Unit
R/C
R/C
up to
64
units of
A/Cs and equipment
Remote Control
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...