InteliLite4 AMF20 Global Guide
572
Description
This alarm evaluates the Mains phase voltage in phases 1. The following
setpoints are related to it:
Mains Underfrequency (page 279)
Mains < > Frequency Delay (page 281)
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Current Unbalance
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
Current Unbalance BOC (page 263)
adjusts the maximum allowed
difference between the highest and lowest phase current at any given
time.
Current Unbalance BOC Delay (page 263)
adjusts the alarm delay.
BOC Current Unbalance
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Overload
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period
longer than the delay. The behavior of the overload alarm is adjusted by the
following setpoints:
adjusts the overload limit.
adjusts the delay
BOC Overload
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Short Circuit
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
adjusts the short current limit
Short Circuit BOC Delay (page 262)
adjusts the delay in fine steps
BOC Short Circuit