InteliLite4 AMF20 Global Guide
451
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
218
Description
This binary input enables or disables
and
if
is adjusted to value "LBI Enable".
Geo-Fencing Enable
back to Logical binary inputs alphabetically
LBI: H
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
192
Description
Binary input has the same function as Horn reset
button on the InteliLite 4 front panel.
Horn Reset Button
back to Logical binary inputs alphabetically
LBI: I
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
624
Description
This binary input changes cooling speed from nominal to idle.
Idle Speed
back to Logical binary inputs alphabetically
LBI: M
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
622
Description
If the input is active, the automatic start of the Gen-set at Mains failure is blocked. In case of running Gen-
set in AUTO mode, timer
is started and when it elapses GCB is opened,
Gen-set goes to cooling procedure and stops. When GCB is opened after
the
MCB is closed.
Note:
This input simulates healthy Mains.
Mains Fail Block