InteliLite4 AMF20 Global Guide
516
Input
Type
Negation
Range
Function
Input 1
Analog
No
Any
Compared value
Input 2
Analog
No
Same as Input 1
Comparative level
Delay
Analog
No
0.0..3000,0 [s]
Comparative delay
Outputs
Output
Type
Negation
Range
Function
Output
Binary
No
0/1
Comparator output
Description
The block works as an analog switch. It compares the input value with the comparative level. The output
will switch on if the input is equal or higher than the comparative level for time longer than the delay.
Image 8.65 Principle of delay
Image 8.66 Configuration of Comp Time block
Note:
Input 2 and Delay can be constants or values from controller.
Group: Time functions
PLC group
Time functions
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
38
Inputs
Timer