InteliLite4 AMF20 Global Guide
490
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
1258
Description
This output is active when controller is in MAN mode and the engine is stopped and it is possible to start it
i.e. no red alarm is activated or
is active (Output
is active).
Manual Ready
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
34
Description
This output provides 1s pulse when:
MCB button is pressed on the controller front facia or
MCB button is pressed on any of external local/remote terminals or
MCB command is received via communication line or
the input MCB B
UTTON
is activated.
MCB Button Echo
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2697
Description
LBO is active as long as it's button is pressed or it's LBI is active.
MCB Button State
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
45
Description
The output controls the mains circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note:
InteliLite 4 controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
MCB Close/Open