InteliLite4 AMF20 Global Guide
148
Double-click on a free input position or existing input to add new input or edit the existing one.
Select the source for the input.
If you create a binary input, you can select a source from the following categories:
Bin. values – this category contains all binary values available in the controller as binary inputs,
logical binary outputs, fixed protection states, user buttons, user protection states.
PLC outputs – this category contains all PLC blocks binary outputs available in the controller.
If you create an analog input, you can select a source from the following categories:
Ana. values – this category contains all analog values available in the controller as analog inputs,
electrical values, values from ECU etc.
All setpoints – this category contains all setpoints of the controller except the dedicated PLC
setpoints. Names, resolutions and dimensions of these setpoints can not be modified.
Image 5.41 PLC inputs
Outputs
Sheet output is located at the right side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free output position to add a new sheet output.
Double-click on an already created output to configure the output onto a controller output terminal or a
logical binary input (first some PLC block output must be connected to this output to enable configuration
of output).