InteliLite4 AMF20 Global Guide
113
For generator voltage from 10 V to < 50 % of nominal voltage, Wrn Stop Fail has delay 1 s
For generator voltage > 50 % of nominal voltage, Wrn Stop Fail has delay 200 ms
Oil pressure >
Starting Oil Pressure (page 228)
, Wrn Stop Fail has delay 1 s
Binary input
is in logical 0, Wrn Stop Fail has delay 1 s
For detected RPM, there is no delay.
Stop engine conditions
If no engine running conditions are validated, then the controller will wait extra 12 s before leaving the
Machine Stop state and releasing the
output.
Image 5.17 Engine stops in
If the total stopping time will exceed setpoint
then the
and
binary outputs for stopping are activated. The controller will continuously try to stop the engine.
Image 5.18 Engine stops after first