InteliLite4 AMF20 Global Guide
502
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
32
Description
This output provides 1s pulse when:
Stop button is pressed on the controller front facia or
Stop button is pressed on any of external local/remote terminals or
Stop command is received via communication line or
the input S
TOP
B
UTTON
is activated.
Stop Button Echo
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2694
Description
LBO is active as long as it's button is pressed or it's LBI is active.
Stop Button State
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
25
Description
Output is active for 1 second after
output activation. This signal is sent to ECU
in case of engine stop request.
Image 8.58 Stop Pulse
Stop Pulse
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
23
Description
Stop Solenoid