InteliLite4 AMF20 Global Guide
215
Subgroup: Frequency settings
Nominal Frequency
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
30 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
8278
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Frequency 2 (page 378)
and
Nominal Frequency 3 (page 383)
.
Gear Teeth
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
FGen->RPM / 1 .. 500 [-]
Default value
FGen->RPM
Alternative config
NO
Step
1
Comm object
8252
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to zero if no pick-up is used and
the Engine speed will be counted from the generator frequency.
Note:
If no pickup is used, the D+ or W terminal should be used to prevent possible overcranking,
which can occur if at least 25% of nominal generator voltage is not present immediately after
exceeding firing speed.