InteliLite4 AMF20 Global Guide
240
Subgroup: Stopping Timers
Cooling Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 3 600 [s]
Default value
30 s
Alternative config
NO
Step
1 s
Comm object
8258
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Stop Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 600 [s]
Default value
60 s
Alternative config
NO
Step
1 s
Comm object
9815
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Under normal conditions the engine must certainly stop within this period after the
has been de-energized and the
energized. The Stop Solenoid output is
deactivated 12 s after last running engine indication went off.
Image 8.7 Stop Time 1