InteliLite4 AMF20 Global Guide
471
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2446
Description
This LBO is active when the engine Particulate Control Diagnostic System detects removal of DPF, loss of
DPF function or failure of PCD itself.
Note:
LBO is required in Yanmar engine types
ATT PCD Lamp
back to Logical binary outputs alphabetically
LBO: C
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2091
Description
Logical binary output for choke valve control. Output C
HOKE
is activated every time when logical binary
output
is activated. Output is deactivated when one of these conditions is fulfilled:
Choke Time is elapsed
Generator voltage is higher than Choke Voltage
Logical binary input Choke Inhibit is activated
Or when some of these situations during start occurs:
Any second level alarm
Emergency stop
Stop command
Cranking pause
Choke
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
74
Description
The output is active when Gen-set is in Cooling state.
Cooling
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
Description
LBO is active as long as it's button is pressed or it's LBI is active.
Start Button State