InteliLite4 AMF20 Global Guide
501
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
in Engine Settings group. Cranking fail pause is adjusted by setpoint
Cranking Fail Pause (page 226)
Image 8.57 Starter
The starter output opens when:
Starting RPM are reached
the "firing" speed is reached (gas engines only)
maximum time of cranking is exceeded
request to stop comes up
D+ value is higher than
Oil pressure value is higher than
Starting Oil Pressure (page 228)
Generator voltage >25 % of
Nominal Voltage Ph-N (page 211)
or
(any phase)
Starter
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
26
Description
Logical binary output which is still in logical 0.
Still Log 0
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
27
Description
Logical binary output which is still in logical 1.
Still Log 1