D+ Threshold
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0..100 [%]
Default value
80 %
Alternative config
NO
Step
1 %
Comm object
14959
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts threshold level for
D+ Delay
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
1..255 [s]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
14960
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts delay for
. This delay is used for:
Alarm
Wrn Charging Alternator Fail (page 537)
For engine running condition – disengagement of starter
D+ Alarm Type
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
No Protec/Wrn/Sd [-]
Default value
Wrn
Alternative config
NO
Step
[-]
Comm object
15751
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if setpoint
is not set to
Disabled
value.
Description
This setpoint adjusts type of alarm
Wrn Charging Alternator Fail (page 537)
.