InteliLite4 AMF20 Global Guide
226
Maximum Cranking Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
1 .. 255 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8256
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Maximum time limit of cranking time.
Cranking Fail Pause
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
5 .. 60 [s]
DefaultFixed
value
8 s
Alternative config
NO
Step
1 s
Comm object
8257
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Pause between
.
output is active in this pause until
Cranking Fail Pause elapses.