InteliLite4 AMF20 Global Guide
228
Starting Oil Pressure
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Disabled / 0,1 .. 10,0 [bar]
Default value
4,5 bar
Alternative config
NO
Step
0,1 bar
Comm object
9681
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Oil pressure limit for starting. The controller will stop cranking (
goes OFF) if the oil
pressure rises above this limit.
Option Disabled – when this option is selected, Oil Pressure value (value from CU analog Oil Pressure,
value from ECU analog Oil pressure and state of binary input Oil Pressure) is not used for disengagement
of starter and for engine running evaluation.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Glow Plugs Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0.0 ..
[s]
Default value
0.1 s
Alternative config
NO
Step
1.0 s
Comm object
14412
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint defines the time before starting when logical binary output
will be
active.