InteliLite4 AMF20 Global Guide
484
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
77
Description
This output is active when the generator voltage, frequency and voltage unbalance is within limits. It is
deactivated:
immediately when the voltage/frequency/voltage unbalance gets out of limits (when GCB is not
closed)
or
with an appropriate delay after the voltage/frequency/voltage unbalance has got out of limits (when
GCB is closed)
Generator Healthy
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
1252
Description
This output is dedicated for diesel engine only. This output will be active for exact time pre-set by setpoint
before every starting attempt. The output is deactivated at the same time
as the
output is activated (100 ms after
output is deactivated).
Image 8.41 Glow Plugs
Glow Plugs