InteliLite4 AMF20 Global Guide
475
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
958
Description
Signal for starting and stopping of ECU.
ECU Run Stop
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
959
Description
This output is active when ECU Wait To Start Lamp is active.
ECU Wait To Start
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
349
Description
This output is active when the ECU sends an active “yellow lamp” flag, i.e. it has detected a non-critical
malfunction. This flag is taken from the DM1 frame on standard J1939 ECUs. Some ECUs provide this flag
in their own proprietary frames and some do not provide the flag at all.
ECU Yellow Lamp
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2410
Description
LBO Electrical Alarm is active when any of generator protections of any alarm level type (Overload, Short
Circuit, IDMT Overcurrent, Current Unbalance, Overvoltage, Undervoltage, Voltage Unbalance,
Overfrequency, Underfrequency, Reverse Power) is active.
LBO Electrical Alarm is deactivated by confirmation of generator protection alarms in alarmlist and
simultaneously generator protections alarms has to be inactive.
Electrical Alarm