InteliLite4 AMF20 Global Guide
239
Run Only Block Delay
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
5.0 s
Alternative config
YES
Step
0.1 s
Comm object
10023
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
During the start of the Gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
The protection blocking is based on the operating state of the engine automat. Once the engine automat
reaches the state "Running" the protection with this blocking condition gets unblocked after delay Run
Only Block Delay.
Subgroup: Stopping
Cooling Speed
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Idle / Nominal [-]
Default value
Nominal
Alternative config
NO
Step
[-]
Comm object
10046
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Selects the function of the binary output
during engine cooling state.
Idle
Cooling is executed at Idle speed and generator protections are switched off.
Nominal
Cooling is executed at Nominal speed and generator protections are active.
Note:
When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note:
Binary output
must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.