InteliLite4 AMF20 Global Guide
513
PLC group
Basic logical functions
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
39
Inputs
Input
Type
Negation
Range
Function
Input 1 .. 2
Binary
Yes
0/1
Inputs 1 .. 2
Outputs
Output
Type
Negation
Range
Function
Output
Binary
Yes
0/1
Result of the logical operation
Description
The block provides logical function of two values - XOR or RS flip-flop. Both inputs and output can be
inverted.
Input 1
Input 2
Output
0
0
0
0
1
1
1
0
1
1
1
0
Function XOR
The block contains a setting for RS dominance. This setting is available in the block dialog window (i.e.
this setting is constantly set by configuration and cannot be changed dynamically in operation).
Input 1 (S)
Input 2 (R)
R-latch
S-latch
E-latch
JK-latch
Q
0
0
Q
-1
Q
-1
Q
-1
Q
-1
0
1
0
0
0
0
1
0
1
1
1
1
1
1
0
1
Q
-1
NOT(Q
-1
)
Function RS
Ext. XOR/RS