InteliLite4 AMF20 Global Guide
219
Reset To Manual
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Disabled / Enabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9983
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm in
the alarm list and fault reset button is pressed. This is a safety function that prevents the Gen-set starting
again automatically in specific cases when fault reset button is pressed.
Backlight Timeout
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Disabled / 1 .. 255 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
10121
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then
the display will be backlighted all the time.