InteliLite4 AMF20 Global Guide
286
Load Reconnection Delay
Setpoint group
Load Management
Related FW
1.3.0
Range [units]
0 .. 600 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8893
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if
Load Shedding Active (page 284)
is enabled
Description
This setpoint is used to proceeds the lower Load shedding stage. When Gen-set load drops under
for more than this delay time, the binary output for higher stage is
opened. Automatic load reconnection works only when
Auto Load Reconnection (page 286)
= Enabled
Auto Load Reconnection
Setpoint group
Load Management
Related FW
1.3.0
Range [units]
Disabled / Enabled [-]
Default value
Enabled
Alternative config
NO
Step
[-]
Comm object
9649
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if
Load Shedding Active (page 284)
is enabled
Description
Switch between manual and automatic reconnection of shedded load..
Disabled
Rising edge on binary input
resets
controller to the lower stage, but only if the load is under the
.
Load Reconnection Delay (page 286)
is not taken into account in
this case.
Enabled
Load reconnection is automatic depend on setpoints
and
Load Reconnection Delay (page 286)
. Binary input
has no function.