Related FW
1.3.0
Related applications
AMF, MRS
Comm object
60
Description
This input is used for manual reconnection of the last disconnected part of the load, if the load has dropped
below the setpoint
Load Reconnection Level (page 285)
. This works only if automatic reconnection is
disabled, i.e. the setpoint
Auto Load Reconnection (page 286)
= Disabled.
Manual Load Reconnection
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
194
Description
This binary input has the same function as MCB button
on the InteliLite 4 front panel. It is evaluated in
MAN mode only.
MCB Button
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
124
Description
When this LBI is active, it is not possible to close MCB – LBO MCB Close/Open, MCB ON Coil cannot be
activated by panel MCB close button, or close command or by auto command.
MCB Disable