InteliLite4 AMF20 Global Guide
140
Short period mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint
Timer 1
Setup
.
Note:
First, the timer functions must be adjusted via setpoint
.
Image 5.33 Short period mode – InteliConfig
In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of
first occurrence of timer. Also adjust the duration of each occurrence of timer. Then select the interval of
repetition (shorter than 1 day).
Example:
On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be activated again every 4th hour for 1 hour.
Set-up via controller interface
In controller go to the Scheduler setpoint group. Select the function of timer via
setpoint. Then go to
Timer 1 Setup
and press the Enter button. In
setpoint
select Repeated mode. Then adjust
Timer 1 First Occur. Date (page 293)
and
. In setpoint
, select Short
Period and adjust
Timer 1 Refresh Period (page 298)
(interval of repetition).
Note:
Use the Left and the Right buttons to move between timer setpoints.
5.5.15 Voltage phase sequence detection
The controller detects phase sequence voltage terminals. This protection is important after controller
installation to avoid wrong voltage phase connection. The phase sequence is adjusted via setpoint