InteliLite4 AMF20 Global Guide
192
Reading Nominal power
Export table of values from InteliConfig
Table: Values
Allowed MODBUS functions: 03, 04
Register
address
Com.Obj.
Name
Dimension
Type
Len
Dec
Min
Max
Group
01227
9018
Nominal
Power
kW
Integer
2
0
0
32767
Generator
Request: (Numbers in Hex)
01
03
04
CC
00
01
45
05
Controller address
Modbus function
Register address
04CC
hex
=
1228
dec
Number of registers
CRC
Response: (Numbers in Hex)
01
03
02
00
C8
B9
D2
Controller address
Modbus function
Length of data
02
hex
= 2 bytes
read
Data
00C8
hex
=
200
dec
CRC
Read nominal power is 200 kW.