InteliLite4 AMF20 Global Guide
316
Subgroup: Timer 4
Timer 4 Function
Setpoint group
Scheduler
Related FW
1.3.0
Range [units]
Disable / Manual On / No Func / TEST / Test OnLd / MFail Blk / Rem Start/Stop / Auto
Run / Mode OFF [-]
Default value
No Func
Alternative config
NO
Step
[-]
Comm object
15361
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is possible to choose from following Timer functions. Binary output
is
always activated when Timer is active regardless of chosen timer function. Timer functions require
controller running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if
is configured for OFF mode
and
is over the same time configured for AUTO mode, controller will work in
OFF mode.
Controller activates timer whenever it is powered up even in period, where timer should be already
running.
Disable
The Timer is disabled.
Manual On
LBO Timer is active, but the Timer itself is disabled.
Note:
This function serves for testing purposes.
No Func
There is no any other function, only binary output of timer is activated.
Mode OFF
When this option is chosen then the binary output of timer is internally connected to
the
binary input.
Rem
Start/Stop
When this option is chosen then the binary output of timer is internally connected to
the
binary input.
TEST
When this option is chosen then the binary output of timer is internally connected to
the binary input
TEST OnLd
When this option is chosen then the binary output of timer is internally connected to
the
binary input.
MFail Blk
When this option is chosen then the binary output of timer is internally connected to
the
binary input.