InteliLite4 AMF20 Global Guide
456
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
88
Description
This is the input of the Pulse Counter 2 function. The module counts pulses at the input and if the input
pulses counter reaches value given by the setpoint
Conversion Coefficient Pulse 2 (page 254)
the
counter value
is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Note:
Recommended length of the pulse is 500 ms.
Pulse Counter 2
back to Logical binary inputs alphabetically
LBI: R
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
61
Description
Closing of the GCB in MRS or transferring of the load from the mains to Gen-set in AMF.
Application
TEST
Remote TEST On Load
MRS
Gen-set started
and running until
the TEST mode
deactivated.
Active:
Gen-set is put to TEST mode. On the top of it the GCB is
closed. The same behavior like the
.
Inactive:
Gen-set comes back to the original mode and behaves
accordingly to this mode and other conditions.
AMF
Gen-set started
and running until
the TEST mode
deactivated.
Active:
Gen-set is put to TEST mode. On the top of it the load is
transferred to the Gen-set.
Inactive:
Gen-set comes back to the original mode and behaves
accordingly to this mode and other conditions. (the load can be
transferred back to the mains (OFF, AUTO) or stay on the Gen-
set (MAN).
Rem TEST On Load