Alarm Type
SD
Alarmlist message
Sd Charging Alternator Fail
Alarm evaluated
Engine running only
Related applications
AMF, MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than
of the controller supply voltage. This alarm
works similar to the red "battery" alarm indicator on a vehicle dashboard. The
setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Wrn Charging Alternator Fail
back to List of alarms level 2
Alarm Type
WRN
Alarmlist message
Wrn Stop Fail
Alarm evaluated
While the engine shall be stopped
Related
applications
AMF, MRS
Description
This alarm occurs if the Gen-set shall be stopped, but some symptom indicates that
it is not stopped. The period when the Gen-set shall be stopped begins after the
has been switched off and time delay
has elapsed and lasts for the entire time the
or
are off.
Image 8.72 Stop Fail
Note:
Gen-set cannot be started until this alarm is inactive and reset.
Wrn Stop Fail
back to List of alarms level 1
Alarm Type
WRN
Alarmlist message
Wrn Maintenance Timer 1 RunHours
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm is active when the value
Maintenance Timer 1 RunHours (page
reaches 0.
The value is adjustable by setpoint
Maintenance Timer 1 RunHours (page
Wrn Maintenance Timer 1 RunHours