InteliLite4 AMF20 Global Guide
460
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
621
Description
The controller is switched to the TEST mode (there are fourthree modes OFF / MAN / AUTO / TEST) when
this binary input is active. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote TEST
back to Logical binary inputs alphabetically
LBI: S
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
44
Description
If this input is active, all alarms except Emergency Stop and Overspeed are suppressed. The suppressed
alarms will be displayed in the alarm list, but they will not take effect regarding the Gen-set control.
Note:
is indicated in the alarm list if Sd Override mode is active to inform the
operator that the engine is not protected.
IMPORTANT: MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN-SET!
Note:
User protection Sd Override is not blocked
Sd Override
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
68
Description
Start of the Gen-set is blocked if this binary input gets active before Start command is issued. While start is
blocked, alarm ALI Start Blocking is active.
Activation of this LBI while Gen-set is already running (or is about to be started) has no effect.
When LBI is active before Start command, the LBO
is not active.
Start Blocking