InteliLite4 AMF20 Global Guide
498
LBO: R
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
62
Description
The binary output is active when the engine is stopped and it is possible to start it i.e. no red alarm is
activated or
is active.
The binary output is switch on when the Ready state occurs.
The binary output is switch off when the Prestart or the Not Ready or the Stop state occurs i.e. always
except Ready state.
Ready
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
324
Description
the output is active if the Gen-set is ready to start automatically and take the load if the mains fails, i.e.:
the controller is in AMF operating mode
the controller is in AUTO controller mode and
no red alarm is present in the alarmlist
when the red alarm is confirmed during Stop Valve and other requirements are fulfilled then the
LBO is still inactive until the state ready
Ready To AMF
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
58
Description
the output is active whenever the GCB is closed or can be closed i.e. the stabilization phase is finished,
the Gen-set is running and the
Minimal Stabilization Time (page 237)
timer has elapsed and the Gen-
set voltage and frequency are within limits.
If GCB is open then Gen-set voltage and frequency must be in limits.
If GCB is close then Gen-set voltage and frequency can be out of limits, but protection delay can’t be count
down. If Gen-set voltage and frequency will return into limits until delay is count down then output is still
active.
Ready To Load