InteliLite4 AMF20 Global Guide
543
Description
This alarm evaluates the generator phase to phase voltage between phases 3
and 1. The following setpoints are related to it:
Generator Undervoltage Wrn (page 265)
Generator <> Voltage Delay (page 266)
back to List of alarms level 1
Alarm Type
WRN
Alarmlist message
Generator > Frequency
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator overfrequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency Wrn (page 267)
Generator <> Frequency Delay (page 268)
Wrn Generator Overfrequency
back to List of alarms level 1
Alarm Type
WRN
Alarmlist message
Generator < Frequency
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator underfrequency in the phase L1. The
following setpoints are related to it:
Generator Underfrequency Wrn (page 267)
Generator <> Frequency Delay (page 268)
Wrn Generator Uderfrequency
back to List of alarms level 1
Alarm Type
WRN
Alarmlist message
Overload
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm is issued when the Gen-set power is over the limit for time period
longer than the delay. The following setpoints are related to it:
adjusts the overload limit.
Overload Del adjusts the delay.
Wrn Overload
back to List of alarms level 1
Alarm Type
WRN
Alarmlist message
All the time
Wrn Battery Overvoltage