InteliLite4 AMF20 Global Guide
265
Generator Undervoltage Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Undervoltage BOC (page 265)
..
Generator Overvoltage Wrn (page
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
9687
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Undervoltage BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0 ..
Generator Undervoltage Wrn (page 265)
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
8293
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.