InteliLite4 AMF20 Global Guide
259
Subgroup: Maintenance Timer 3
Maintenance Timer 3 RunHours
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
0 ... 9 999 [h] / Disabled
Default value
Disabled
Alternative config
NO
Step
1 h
Comm object
13855
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer counts down when engine is running. If it reaches zero, an alarm appears, but the timer
still counts down to negative values. When the value 10 000 (Disabled) is set, the Maintenance function is
disabled and the counter value disappears from controllers statistics.
Reset of the timer can be done by adjusting this setpoint again.
Maintenance Timer 3 Interval
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
1 .. 36 [month] / Disabled
Default value
Disabled
Alternative config
NO
Step
1 month
Comm object
20585
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer counts down all the time, setting is done in months, but actual
value is displayed and counted in days. If it reaches zero, an alarm appears, but the
timer still counts down to negative values. When the value 37 (Disabled) is set, then the maintenance
function is disabled and counter does not count and the counter value disappears from controllers
statistics.
Reset of the timer can be done by adjusting this setpoint again. Setting of the setpoint does not change
when the reset is done, only the
Maintenance Timer 3 Interval (page 414)
value changes to reflect reset
of the maintenance timer.