InteliLite4 AMF20 Global Guide
377
Nominal Power Split Phase 1
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
YES
Step
1 kW
Comm object
15771
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal power of the Gen-set for detected split-phase or mono phase connection. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Autodetect and
Autodetect detects connection type as Monophase or SplitphaseL1L2 or SplitphaseL1L3.
Note:
This value is used when any other alternate configuration is not active.
Subgroup: Configuration 2
Nominal RPM 2
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
100 .. 4000 [RPM]
Default value
1 500 RPM
Alternative config
YES
Step
1 RPM
Comm object
9916
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note:
This value is used when binary input
is active.