InteliLite4 AMF20 Global Guide
486
LBO: H
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
81
Description
This output toggles on/off in a period of 500 ms whenever the controller is switched on and functional.
Heartbeat
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
1
Description
The output designed to be used for acoustic indication of a newly appeared alarm. The output is activated
each time a new alarm has appeared and remains active until one of the following events occurs:
Fault reset
is pressed
Horn reset
is pressed
has elapsed
Horn
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
31
Description
This output provides 1s pulse when:
Horn Reset button is pressed on the controller front facia or
Horn Reset button is pressed on any of external local/remote terminals or
Horn Reset command is received via communication line or
the input H
ORN
R
ESET
B
UTTON
is activated.
HornRes Button Echo
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2696
Description
LBO is active as long as it's button is pressed or it's LBI is active.
HornRes Button State