InteliLite4 AMF20 Global Guide
220
Horn Timeout
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Disabled / 1 .. 599 s / Horn Reset [-]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8264
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Setting of horn behavior.
Disabled
Disabling the Horn sounding function
1 .. 599 [s]
Timeout for
binary output. The
output is active
when this timeout elapsed.
Horn reset
LBO
is deactivated by Fault reset button or by Horn reset button.
Note:
Horn timeout starts again from the beginning if a new alarm appears before previous Horn
timeout has elapsed.
Fail Safe Binary State
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
[-]
Default value
Last valid state
Alternative config
NO
Step
-
Comm object
21215
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint adjusts behavior of the controller when the received binary input values from CAN Extension
Module, EFCP Module and ECU modules are invalid due to the loss of communication with peripherals.
Log0
All invalid values are replaced by logical zero.
Log1
All invalid values are replaced by logical one.
Last Valid State
All invalid values are replaced by the last valid state.