50
4.4.8 Binary Outputs
Use min. 1 mm
2
cables for wiring of binary outputs. Use external relays as indicated on the schematic below
for all outputs except those where low-current loads are connected (signalization etc.).
IMPORTANT: Use suppression diodes on all relays and other inductive loads!
Image 4.42 Binary outputs wiring
Note:
Every single low current binary output can provide up to 0.5 A of steady current.
IMPORTANT: Binary output 1 and 2 is power up by E-Stop terminal.
IMPORTANT: When operating temperature is higher than 60 °C it is strongly recommended to
limit output current of high current binary outputs to 4 A (each).